Heyco-Flex非金属软管接头180°
FITS CONDUIT/ TUBING TRADE SIZE | PART NO. | DESC. | THREAD SIZE | PART DIMENSIONS BODY AND SEALING UNIT | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Black | Gray | A Clearance Hole | B Max. O.A. Length | C Thread Length | D | E | |||||||||
Wrenching | |||||||||||||||
Nut Thk. | Flat Size | ||||||||||||||
in. | mm. | in. | mm. | in. | mm. | in. | mm. | in. | mm. | ||||||
1/4 | 8398 | - | HFC 1/4-PG7* | PG7 | .492 | 12,5 | 1.13 | 28,7 | .45 | 11,4 | .21 | 5,3 | 1.00 | 25,4 | |
3/8 | 8400 | 8401 | HFC 3/8 | 1/2˝ NPT | .875** | 22,2 | 1.96 | 49,8 | .63 | 16,0 | .25 | 6,3 | 1.33 | 33,7 | |
1/2 | 8402 | 8403 | HFC 1/2 | ||||||||||||
3/4 | 8404 | 8405 | HFC 3/4 | 3/4˝ NPT | 1.109 | 28,1 | 2.04 | 52,8 | .63 | 16,0 | .25 | 6,3 | 1.56 | 39,6 | |
1 | 8406 | 8407 | HFC 1 | 1˝ NPT | 1.375 | 34,9 | 2.25 | 57,2 | .78 | 19,8 | .25 | 6,3 | 1.81 | 46,0 | |
1-1/4 | 8638 | 8639 | HFC 1-1/4† | 1-1/4˝ NPT | 1.734 | 44,0 | 2.07 | 52,6 | .69 | 17,4 | .25 | 6,3 | 2.15 | 54,6 | |
1-1/2 | 8640 | 8641 | HFC 1-1/2† | 1-1/2˝ NPT | 1.984 | 50,4 | 2.28 | 57,9 | .72 | 18,3 | .28 | 7,0 | 2.40 | 61,0 | |
2 | 8642 | 8643 | HFC 2† | 2˝ NPT | 2.469 | 62,7 | 2.26 | 66,0 | .85 | 21,6 | .31 | 7,9 | 2.98 | 75,6 |
Standard colors black and gray.
*Standard color black. Recognized under UL file E121095. See PG-7 thread specification.
**Fittings use same mounting hole size but attach two different conduit sizes.
† Certified cULus under file E28430
No disassembly required. Instead, the installer simply pushes the conduit or tubing onto the ferrule, then tightens the domed sealing nut. This completed assembly can then be secured in the panel by the locknut or into an NPT threaded hole.
Convex ferrule ensures liquid tight seal.
No threading of the conduit or tubing is required to install. This eliminates the possibility of cutting the conduit and creating leak paths.
Complete conduit/connector system is reusable. Conduit will not wind tight onto the connector during assembly and can be easily removed by pulling while turning in a clockwise direction.
Multiple sizes for use with Heyco-Flex Conduit and Tubing.
Suitable for indoor/outdoor use; for original equipment manufacturers or field installers.
Use of a sealing washer may be required for wet locations.
All nylon construction resists salt water, weak acids, gasoline, alcohol, oil, grease, and common solvents. (This feature is not assessed by UL certification and testing.)
If using a tapped hole, Teflon® tape is needed on the threads of the connector, for all other applications an O-ring and Locknut are needed to attain liquid tight.
Black connectors up to 1˝ provided with nylon locknut, packed separately. O-ring sold separately, click here.
Black connectors larger than 1˝ and all gray connectors provided with assembled O-ring and metal locknuts.
Metal locknuts: NPT, PG, and Metric.
Nylon locknuts: NPT, PG, and Metric.
Material | Nylon 6/6 | |
---|---|---|
Certifications | Listed under Underwriters' Laboratories File E28430 | |
Certified by Canadian Standards Association File 84579 & 81067 | ||
Flammability Rating | 94V-2 | |
Temperature Range | -22°F (-30°C) to 221°F (105°C) | |
IP Rating | IP 68 up to 70 psi (5 bar) water pressure |